CCW Cooling coils
CCW Cold water coils are an ideal cooling solution where water cillers are installed. CCW can be used with all of our current range of units: VEX100, VEX200 og VEX340-350-360.
Information on CCW are included in the product informations for EXHAUSTO's air handling units.
| CCW for | VEX140 | VEX150 | VEX160 | VEX170 |
| Rows of pipes | 4 | 5 | 4 | 4 |
| Circuits | 8 | 13 | 17 | 16 |
| Face area (HxW) [mm] | 500x610 | 525x760 | 650x1000 | 762x1250 |
| Pipe connection [DN] | 25 | 32 | 32 | 32 |
| Distance between fins [mm] | 2,8 | 3,0 | 2,5 | 2,8 |
| Weight uninsulated [kg] | 39 | 49 | 54 | 72 |
| Weight insulated [kg] | 72 | 87 | 135 | 165 |
| Water capacity [l] | 3,5 | 5,8 | 7,5 | 18,7 |
| Test pressure [kPa]: 3000 | Max. operating pressure [kPa]: 1600 | |||
| CCW for | VEX240 | VEX250 | VEX260 | VEX270 | VEX280 |
| Rows of pipes | 4 | 5 | 4 | 4 | 4 |
| Circuits | 8 | 13 | 17 | 16 | 40 |
| Face area (HxW) [mm] | 500x610 | 525x760 | 650x1000 | 762x1250 | 1000x1600 |
| Pipe connection [DN] | 25 | 32 | 32 | 32 | 50 |
| Distance between fins [mm] | 2,8 | 3,0 | 2,5 | 2,8 | 2,5 |
| Weight uninsulated [kg] | 39 | 49 | 54 | 72 | 65 |
| Weight insulated [kg] | 72 | 87 | 135 | 165 | 202 |
| Water capacity [l] | 3,5 | 5,8 | 7,5 | 18,7 | 24,0 |
| Test pressure [kPa]: 3000 | Max. operating pressure [kPa]: 1600 | ||||
| CCW for | VEX340 | VEX350 | VEX360 |
| Rows of pipes | 4 | 3 | 3 |
| Circuits | 8 | 6 | 6 |
| Face area (HxW) [mm] | 500x610 | 700x800 | 700x800 |
| Pipe connection [DN] | 25 | 25 | 25 |
| Distance between fins [mm] | 2,8 | 2,5 | 2,5 |
| Weight uninsulated [kg] | 39 | 18,5 | 18,5 |
| Weight insulated [kg] | 72 | - | - |
| Water capacity [l] | 3,5 | 7,4 | 7,4 |
| Test pressure [kPa]: 3000 | Max. operating pressure [kPa]: 1600 | ||
last updated 10-31-2011